What is a Dead End Corridor?

Skwerl
4 min readMar 20, 2016

Any pathway longer than 20 ft with no exit.

IBC 2012 Section 1018.4 Dead ends.

Where more than one exit or exit access doorway is required, the exit access shall be arranged such that there are no dead ends in corridors more than 20 feet (6096 mm) in length.

Exceptions:

1. In occupancies in Group I-3 of Occupancy Condition 2, 3 or 4 (see Section 308.5), the dead end in a corridor shall not exceed 50 feet (15 240 mm).

2. In occupancies in Groups B, E, F, I-1, M, R-1, R-2, R-4, S and U, where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the length of the dead-end corridors shall not exceed 50 feet (15 240 mm).

3. A dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.

The requirements of this section apply where a space is required to have more than one means of egress according to Section 1015.1.

Dead ends in corridors and passageways can seriously increase the time needed for an occupant to locate the exits. More importantly, dead ends will allow a single fire event to eliminate access to all of the exits by trapping the occupants in the dead-end area. A dead end exists if the occupant of the corridor or passageway has only one direction to travel to reach any of the building exits [see Figure 1018.4(1)]. While a preferred building layout would be one without dead ends, a maximum dead-end length of 20 feet (6096 mm) is permitted and is to be measured from the extreme point in the dead end to the point where the occupants have a choice of two directions to the exits. Having to go back only 20 feet (6096 mm) after coming to a dead end is not such a significant distance as to cause a serious delay in reaching an exit during an emergency situation.

A dead end results whether or not egress elements open into it. A dead end is a hazard for occupants who enter the area from adjacent spaces, travel past an exit into a dead end or enter a dead end with the mistaken assumption that an exit is directly accessible from the dead end.

Note that Section 402.4.5 deals with dead-end distances in a covered mall and assumes that, with a sufficiently wide mall in relation to its length, alternative paths of travel will be available in the mall itself to reach an exit (i.e., the mall is not to be confused as being a corridor).

Under special conditions, exceptions to the 20-foot (6096 mm) dead-end limitation apply.

Exception 1 is permitted based on the considerations of the functional needs of Group I-3 Occupancy Conditions 2, 3 or 4, the requirements for smoke compartmentalization in Section 408.6 and the requirement for automatic sprinkler protection of the facility in Section 903.2.6.

Exception 2 recognizes the fire protection benefits and performance history of automatic fire sprinkler systems. While the degree of hazard in Group B, E, F, M, S and U occupancies does not initially require an automatic fire suppression system, the length of a dead-end corridor or passageway is permitted to be extended to 50 feet (15 240 mm) where an automatic fire sprinkler system in accordance with NFPA 13 is provided throughout the building. This exception is also permitted in Group I-1, R-1, R-2 and R-4 occupancies. In addition, these provisions are consistent with those in the IEBC and IFC in the regulation of dead-end corridors in existing buildings undergoing alterations.

Exception 3 addresses the condition presented by “cul-de-sac” elevator lobbies directly accessible from exit access corridors. In such an elevator lobby, lengths of 20 to 30 feet (6096 to 9144 mm) are common for three- or four-car elevator banks. Typically, the width of this elevator lobby is such that the possibility of confusion with a path of egress is minimized. Below the 21/2:1 ratio, the dead end becomes so wide that it is less likely to be perceived as a corridor leading to an exit. For example, based on the 21/2:1 ratio limitation, a 25-foot-long (7620 mm) dead end over 10 feet (3048 mm) in width would not be considered a dead-end corridor [see Figure 1018.4(2)]. For additional elevator lobby requirements, see the commentary to Section 708.14.1.

--

--