DC-DC CONVERTER WITH HIGH FREQUENCY TRANSFORMER (DHFT) IN AC/DC MICROGRID

K.Devika ,C.Balaji. M.E., PG scholar ,Assistant Professor

Kings College of Engineering

IJTCSE Research /ISSN 2349–1582 conference publication

Abstract-In this paper, DC/DC converter with High Frequency Transformer (DHFT) is proposed to replace the conventional bulky transformer for bus voltage matching and galvanic isolation. Various DHFT topologies have been compared and CLLC-type has been recommended due to its capabilities of bidirectional power flow, seamless transition and low switching loss. DHFT are designed in order to maximize the conversion efficiency and minimize output voltage variations in different loading condition. This paper presents a series-connected high frequency DC/DC converter connected to a DC microgrid system to provide auxiliary power for lighting, control and communication in a DC light. Three converters with low voltage and current stresses of power devices are series-connected with single transformers to convert a high voltage input to a low voltage output for a DC light. Thus, Metal-Oxide-Semiconductor Field-Effect Transistors (MOSFETs) with a low voltage rating and a turn-on resistance are adopted in the proposed circuit topology in order to decrease power losses on power switches and copper losses on transformer windings. Lab-scale prototypes of the DHFT and hybrid AC/DC microgrid have been developed for experimental verifications. A small hybrid grid will be modelled and simulated using MATLAB.

Keywords- AC/DC microgrid ; DHFT; CLLC; Bidirectional power flow; conversion efficiency

I.INTRODUCTION

DC Microgrid has become popular due to the increasing penetration of DC compatible loads (mainly electronic loads and motors with variable speed drives) and Renewable Energy Sources (RESs)[1,2]. In order to compensate the RESs generation intermittency, localized energy storages, like various electrochemical batteries, ultra capacitor and Lead Acid Battery most of which are DC inherent, are implemented. As a conventional solution, the aforementioned DC sources, storages and loads are connected to the AC network through dedicated DC/AC conversions [3,4].It will induce significant energy loss and reduce system reliability. Alternatively, DC microgrid, which exhibits better compatibility with DC compatible sources, storages and loads, can be the solution. However, the direct DC compatible appliances, which are commercially available, are limited and more costly compared with conventional ones due to low production volume.

Hybrid AC/DC microgrid is proposed as a comprised solution to minimize the number of power conversions and enhance system energy efficiency [5,6]. The Battery and solar PV are connected to the DC bus through respective DC/DC converters and wind turbine is connected to the AC bus through AC/AC conversion. AC and DC loads are supplied from respective bus directly.

The Bidirectional Interlinking Converter (BIC) is used to realize the power flow between AC and DC bus. In this work, replacement of the bulky conventional transformer by DC/DC

converter with High Frequency Transformer (DHFT) is proposed. DHFT is a DC/DC conversion topology with high power density and wide range of voltage boost/buck ratio. At the same time, DHFT conversion can be divided into two stages, namely DC/AC and AC/DC. A high frequency transformer interlinks these two stages, with which, DC sub-grid isolation can also be achieved. The DHFT is installed between the DC bus and BIC DC output. The boost ratio of DHFT is designed so that the voltage magnitude of BIC AC and DC outputs can be matched with the conventional single-stage topology. Compared with the conventional solution as illustrated, implementation of DHFT will help reduction of system weight and space occupation significantly, while retaining the system performance.

CONTROL OF HYBRID AC/DC MICROGRID WITH DHFT

A DHFT prototype has been developed and integrated into the hybrid AC/DC microgrid. A DC programmable source has been used to simulate the BESS for DC bus voltage regulation. The DC load bank tied to the V/DC bus to emulate different loading profiles and also enables bidirectional power flow of BIC and DHFT. The HV side of DHFT is connected to the BIC DC output.BIC AC output is tied to an AC programmable source, which is used to emulate the DG/UG for AC voltage/frequency regulation. Both BIC and DHFT will be simulated using MATLAB.

The schematic diagram of hybrid AC/DC microgrid with implementation of DHFT is shown in fig.1 .DHFT boosts the DC bus voltage to the magnitude such that the voltage at DC and AC outputs of BIC can be matched with single-stage topology. The control algorithm of BIC remains unchanged. BIC is capable of operating in three modes, namely AC Voltage Regulation Mode (VRM), DC VRM and Power Dispatch Mode (PDM), based on the availability of AC and DC sources. Capability of multiple-mode operation of DHFT, which is connected in series with BIC, is expected. It makes both DHFT operating modes and system operating scenarios complicated. What’s worse, instant operating mode transition in accordance to BIC operating modes set a challenge for the communication link between the DHFT/BIC and central controller.

Therefore, open-loop control of DHFT is recommended to reduce the number of system operating scenarios and simplify system control. AC and DC bus voltage regulation are the prime control objectives of hybrid AC/DC microgrid. The DC bus voltage can be controlled by Battery Energy Storage System (BESS) or BIC in DC VRM. The AC voltage/frequency regulation can be realized with Utility Grid (UG), Diesel Generator (DG) or BIC in AC VRM. Therefore, the operating scenarios of hybrid AC/DC microgrid.

In operating scenario 1, BESS outage has occurred due to unavailability of battery bank or converter faults. The AC bus voltage/frequency regulation is controlled by UG/DG, while the DC bus voltage is regulated by BIC in DC VRM. Therefore, the HV side of DHFT is regulated and the power flow is determined by the power balance in DC sub-grid. If PV generation exceeds DC load consumption, the excess power will flow to AC sub-grid through DHFT and BIC.On the other hand, when the residual power is positive, power flow from AC sub-grid to DC sub-grid through DHFT/BIC occurs.

Operating Scenario 2

In operating scenario 2, neither UG nor DG is available. The DC bus voltage is regulated by BESS and BIC is scheduled to operate in AC VRM to control the AC sub-grid voltage and frequency. Similar to operating scenario 1, the LV side of DHFT is regulated and the HV side power flow direction and magnitude is determined based on the power balance in AC sub-grid.

DHFT DESIGN

The criteria of DHFT design include:

High conversion efficiency

Rated conversion ratio with minimum voltage variations in different loading conditions

Autonomous power flow and seamless transitions

circuit is comprised of the capacitors Cr1, Cr2 and leakage inductance Lr1, Lr2. Lm1 is the magnetizing inductance for power transform from AB to CD port. The equivalent circuit diagram of power flow transitions between LV and HV sides is as shown in Fig.2. L1, C1, L2 and C2 denote the equivalent inductance and capacitance of the primary and secondary sides, respectively. Take the power flow from AB to CD. The transmission gain of the DHFT can be normalized as: The relationship between the normalized gain and parameter g can be illustrated as shown in Fig.2. It can be observed that the maximum gain point varies with different g selection, which indicates that the resonant point is related to the secondary capacitor.

However, the maximum transmission gain has kept almost constant with different g values. Therefore, based on the DHFT design, there are many combinations of Cr1 and Cr2 that can achieve the desired transmission gain.

In the proposed hybrid AC/DC microgrid, DHFT operates under the resonant condition to ensure the maximum

transmission power and reduce the switching loss. Moreover, combining the aforementioned analysis, the designed DHFT can ensure satisfactory performance with multiple choices, especially for the resonant capacitors.

SIMULATION AND RESULTS

A DHFT prototype has been developed and integrated into the hybrid AC/DC microgrid test bed as shown in Fig. 3. A DC programmable source has been used to simulate the BESS for DC bus voltage regulation. The DC load bank tied to the 380V/DC bus to emulate different loading profiles and also enables bidirectional power flow of BIC and DHFT.

The HV side of DHFT is connected to the BIC DC output as shown in the figure. BIC AC output is tied to an AC programmable source, which is used to emulate the DG/UG for AC voltage/frequency regulation. Both BIC and DHFT are controlled with Digital Signal Processor (DSP).

CONCLUSION

In this paper, DHFT with CLLC topology has been proposed to replace the conventional bulky transformer in hybrid AC/DC microgrid for BIC voltage matching and galvanic isolation. Different system operating scenarios have been analyzed and open-loop control of DHFT has been recommended to simplify system control algorithm and enhance reliability. Derivations of DHFT design parameters have been carried out as the guidance of prototyping. Various experimental cases have been conducted and the performance of DHFT in hybrid AC/DC microgrid.

REFERENCES

[1] Liu B, Zhuo F, Zhu Y, et al. “System operation and energy management of a renewable energy-based DC micro- grid for high penetration depth application,” IEEE Transactions on Smart Grid, vol. 6, no. 3, pp. 1147- 1155, 2015.

[2] Ito Y, Zhongqing Y, Akagi H. “DC microgrid based distribution power generation system,” Power Electronics and Motion Control Conference, 2004. IPEMC 2004, 3: 1740–1745.

[3] Bevrani H, Habibi F, Babahajyani P, et al. “Intelligent frequency control in an AC microgrid: Online PSO-based fuzzy tuning approach,” IEEE Transactions on Smart Grid, vol. 3, no. 4, pp. 1935–1944, 2012.

[4] Wang P, Liu X, Jin C, et al. “A hybrid AC/DC micro-grid architecture, operation and control,” Power and Energy Society General Meeting, IEEE, 2011: 1–8.

[5] Eghtedarpour N, Farjah E. “Power control and management in a hybrid AC/DC microgrid,” IEEE transactions on smart grid, vol. 5, no. 3, pp. 1494–1505, 2014.

[6] Fan H, Li H. “High-frequency transformer isolated bidirectional DC–DC converter modules with high efficiency over wide load range for 20 kVA solid-state transformer,” IEEE Transactions on Power Electronics, vol. 26, no. 12, pp. 3599–3608, 2011.

[7] Du Y, Baek S, Bhattacharya S, et al. “High-voltage high-frequency transformer design for a 7.2 kV to 120V/240V 20kVA solid state transformer,” IECON 2010–36th Annual Conference on IEEE Industrial Electronics Society. IEEE, 2010: 493–498.

[8] Zhao T, Wang G, Bhattacharya S, et al. “Voltage and power balance control for a cascaded H-bridge converter-based solid-state transformer,” IEEE Transactions on Power Electronics, vol. 28, no. 4, pp. 1523–1532, 2013.

[9] Qin H, Kimball J W. “Solid-state transformer architecture using AC– AC dual-active-bridge converter [J].,” IEEE Transactions on Industrial Electronics, vol. 60, no. 9, pp. 3720–3730, 2013.

[10] G. G. Oggier, G. O. Garc’ıa, and A.

R. Oliva, “Modulation strategy to operate the dual active bridge dc–dc converter under soft-switching in the whole operating range,” IEEE Transactions on Power Electronics, vol. 26, no. 4, pp. 1228–1236, Apr. 2011.

[11] B. Zhao, Q. Yu, and W. Sun, “Extended-phase-shift control of isolated bidirectional dc–dc converter for power distribution in microgrid,” IEEE Transactions on Power Electronics, vol. 27, no. 11, pp. 4667–4680, Nov. 2012.

[12] Chang C H, Chang E C, Cheng H L. “A high-efficiency solar array simulator implemented by an LLC resonant DC–DC converter,” IEEE Transactions on Power Electronics, vol. 28, no. 6, pp. 3039–3046, 2013.

[13] Jiang T, Zhang J, Wu X, et al. “A bidirectional LLC resonant converter with automatic forward and backward mode transition,” IEEE Transactions on Power Electronics, vol. 30, no. 2, pp. 757–770, 2015.

[14] Chen W, Rong P, Lu Z. “Snubberless bidirectional dc–dc converter with new CLLC resonant tank featuring minimized switching loss,” IEEE Transactions on industrial electronics, vol. 57, no. 9, pp. 3075–3086, 2010.

[15] W. Chen and Z. Lu, “Investigation on topology for type-4 LLC resonant dc-dc converter,” in Proc. IEEE Transactions on Power Electronics Spec. Conf., 2008, pp. 1421–1425.

--

--