STACK HEIGHT FOR DIESEL ENGINES (ENGINE RATING MORE THAN 0.8 MW (800 KW)

Mohan Babu V
MechGoals
Published in
Jul 6, 2022

Stack height (for generator sets commissioned after 1.7.2003)

Stack height shall be maximum of the following, in meter:

(i) 14 Q0.3, Q= Total SO2 emission from the plant in kg/hr.

(ii) Minimum 6 m. above the building where generator set is installed.

(iii) 30 m.

--

--